Building services engineering calculators
Heat loss, pipe and duct sizing, plant duty. Done properly, for free.
Standard CIBSE methods, laid out so you can see every step. Method and source on every sheet, so you can check it against your own code before you rely on it.
Calculation register
Pick a sheet. Every calculator shows its method and cites its source.
Why this exists
The checks building services engineers run most often were never in one place. Now they are. Each one is the standard method, laid out so you can see exactly what it's doing.
What's in Pro
Every calculator stays free. Pro is a one-off €10 for the parts you'd put in a design file:
- PDF calc sheets with project, reference, revision and engineer on the header
- Install as an app, works offline on site
- Your own defaults for roughness, U-values and velocity limits
Heating · Sheet 01
Space Heat Loss
Fabric loss (U·A·ΔT per element) plus ventilation and infiltration loss, with the TGD L backstop check on every element.
Fabric loss
| Element | U-value (W/m²K) | Area (m²) | Loss (W) | TGD L backstop |
|---|
The five standard elements are fixed - type the U-value and area for each. Backstops are the TGD L 2022 (Dwellings) Table 1 area-weighted values: pitched roof 0.16, flat roof 0.20, walls 0.18, floors 0.18, windows / doors / rooflights 1.4 W/m²K (verified against the gov.ie PDF, Sep 2026).
Add another element
Garage door, party wall, rooflight, conservatory glazing, exposed soffit - anything not in the list above. Name it, give it a U-value and an area, and it joins the table with its own loss and backstop check (matched on the words wall / roof / floor / window / door).
Ventilation / infiltration loss
Method: Fabric: Σ(U×A×ΔT). Ventilation: 0.33 × ACH × Volume × ΔT (0.33 Wh/m³K ≈ ρ·cp of air). ΔT = internal − external design temp.
Calc sheet PDF for Heat Loss
Pro turns this into a signed-off calc sheet: project, reference, revision and engineer on the header, all inputs and results, method and source. Save it to the design file.
Unlock Pro - €10 once
Water Services · Sheet 02
Pipe Sizing
Flow rate in, velocity and Pa/m out — circular or rectangular, metric or imperial. Limits from CIBSE, the Irish TGDs, British Standards or your own company rules. Demand from BS 8558 loading units if you don't have a flow yet.
Method: Darcy-Weisbach + Colebrook-White (laminar below Re 2300 uses f=64/Re). Rectangular sections use hydraulic diameter for the friction calc. Roughness values are typical starting points — verify against your project spec.
Calc sheet PDF for Pipe Pressure Drop
Pro turns this into a signed-off calc sheet: project, reference, revision and engineer on the header, all inputs and results, method and source. Save it to the design file.
Unlock Pro - €10 once
Ventilation · Sheet 03
Duct Sizing
Flow rate in, velocity and Pa/m out — circular, rectangular or flat oval, metric or imperial. Limits from CIBSE, the Irish TGDs, British Standards or your own company rules. CO₂ build-up and AHU coil load below.
Method: Darcy-Weisbach + Colebrook-White. Rectangular ducts use hydraulic diameter (2ab/(a+b)) for the friction calc — a good approximation for most aspect ratios; very flat/elongated ducts want CIBSE Guide C's additional aspect-ratio correction, not yet included.
Calc sheet PDF for Duct Sizer
Pro turns this into a signed-off calc sheet: project, reference, revision and engineer on the header, all inputs and results, method and source. Save it to the design file.
Unlock Pro - €10 onceCO₂ build-up (indoor air quality)
Model: C(t) = Cout + (G/Q)×(1−e−ACH·t). G = occupants × activity rate. Q = ACH × volume. Assumes a well-mixed room and constant emission rate. Target indoor CO₂ for good cognitive function is typically kept below 800–1000 ppm.
AHU thermal load (simplified)
Method: ventilation airflow Q=ACH×Volume/3600. Air after heat recovery: T₁=Tout+η(Troom−Tout). Required supply temp solved from the internal load at this airflow, clamped to your min/max. Sensible load=ṁ·cp·(Tsupply−T₁). Latent load uses humidity ratios (Magnus approximation) between outdoor-after-HR air and room target RH.
Refrigeration & Heat Pumps · Sheet 04
Heat Pump / AHU / Chiller Duty
Pick what you're sizing first — the right fields show up for it. Then match the load against real Irish supplier ranges.
What are you sizing?
AC Units covers chillers, VRF, and HVRF (hydro VRF) together — each row in the finder below is clearly labeled with which type it is.
Pro
Free to use. €10 to make it yours.
Every calculator stays free, forever, for everyone. Pro is a one-off €10 that unlocks the parts you'd actually put in a design file - no subscription, no account, one licence key.
Individual
- PDF calc sheets - project, ref, rev, engineer on the header, all inputs and results, method cited
- Install as an app on phone or desktop, works offline on site
- Saved projects and batch / schedule mode (rolling out this month)
- Your own defaults - roughness, U-values, velocity limits
- Every new calculator added, no extra charge
Team
- Everything in Individual, for up to 16 engineers
- One key for the office - activate on each device, manage seats in Lemon Squeezy
- Invoice with VAT for the company accounts
Checkout by Lemon Squeezy: card, PayPal, Apple Pay. VAT handled. Your licence key arrives by email straight away - paste it below.
Already have a key?
Calc sheet header
Printed on every Pro PDF. Saved on this device only - never sent anywhere.
Get told when new calculators drop
Pump head & NPSH, fan laws, expansion vessel sizing and cable fill are next. One email per release, nothing else.